ProGap S - 物料填充料位的监测

当前位置:Home · 产品介绍 · ProGap S - 物料填充料位的监测
 

ProGap S -
物位探测

应用非接触式微波技术,测量料仓、管道或筒仓中的固体物料物位

  • 对物料的堆积不敏感
  • 测量范围可达18米(更大范围可定制)
  • 配置适配器可适应220 °C 20 bar
  • 配置陶瓷适配器可以最高适应1000 °C
  • 可应用于防爆场合
  • 信号通过继电器输出
  • 可以在非金属料仓外进行监测
  • 较小的传感器配置独立的信号处理单元

 

- 不受下料过程的影响 -

Use / Function

The ProGap S microwave barrier is a universal sensor with a flexible range of applications, consisting of a transmitter and receiver on the basis of the latest microwave technology. It is used to detect the limit level of dry bulk solids of all types or to position objects. The microwave barrier is a contactless measuring procedure. It can be installed in containers, pipelines, shafts or free-fall sections. The range, depending on the model, is either 0 ... 4 m or 0 ... 18 m. Larger ranges can also be realised. If container walls, housings or pipelines are not metal, it is possible to measure from the outside. This even makes it possible to completely uncouple the measurement from the process through suitable windows (made of non-metallic materials). This is especially interesting in the use of aggressive, abrasive or coarse materials or in cases of extreme pressures and temperatures. With the help of a process adapter, the ProGap S can also be used under difficult conditions such as in dust ex-zones. The use of microwaves also ensures a high level of insensitivity to any caking on the sensor window.

Mounting and Installation

The ProGap S can be easily installed in the following ways:

  • screwing into a G 1½-inch-screw neck
  • with an DN-40-flange or
  • with a clamp or other mounting

The fitting position of the devices is arbitrary. Important is that transmitter and receiver are positioned precisely to each other. The adjustment is made by means of a counter-screw fitting. Commissioning will be done by evaluation unit

Technical Data

Sensor Material Housing: Stainless steel 1.4571 / Sensor isolation: POM
  Protective system IP 65
  Using in EX-Zones As ProGap S Ex-sensor in DustEx-zone 20/22 and GasEx-zone 0/2 only with process-adapter
  Process temperature - 20 ... + 80 °C
- 20 ... + 220 °C (with process-adapter)
up to 1,000 °C (with ceramic flange)
  Ambient temperature - 20 ... + 60 °C
  Working pressure max. 1 bar
max. 20 bar (with process-adapter)
  Detection range 0 ... 4 m
0 ... 18 m
> 18 m (on demand)
  Power supply 24 V DC powered by DIN Rail electronic
  Power consumption approx. 1.8 VA
  Current consumption max. 100 mA
  Measuring frequency K-BAND 24.125 GHz (± 100 MHz)
  Transmitting power max. 5 mW
  Weight Transmitter/Receiver approx. 560 g each
     
DIN Rail electronic Power supply 24 V DC ± 10 %
  Power consumption 3.5 W
  Current consumption 120 mA at 24 V
  Relay (max.)
- Voltage
- Current
- Capacity

250 V AC
1 A
60 W
  Fall-delay time 0.25... 5 s (continuously adjustable)
  Weight approx. 172 g
  Protective system IP 40
     
     
 
 