AirSafe - Monitoreo en continuo de partículas sólidas en el aire del ambiente

Ellos están aquí:Home · Productos · AirSafe - Monitoreo en continuo de partículas sólidas en el aire del ambiente
 

AirSafe -
Monitoreo en continuo de partículas
sólidas en el aire del ambiente

  • Para evitar la creación de áreas de riesgo de explosiones por concentración de polvo.
  • Concentraciones de polvo en los lugares de trabajo se supervisan continuamente.
  • Detección de posibles escapes de polvo de las diferentes partes del sistema son rápidamente detectados.

  • También para aplicaciones en zonas 22 con polvos

 

 

 

 

Use

Triboelectric sensor technology from SWR has proven itself in thousands of applications for measuring dust concentrations in process systems. 
AirSafe is a new measuring instrument which can monitor the dust concentration in ambient air, for example in control system areas, silo areas, boiler houses or work stations.
AirSafe monitors concentrations on the basis of pre-set limit values.
For example, to avoid the accumulation of dust in explosion zones or to detect unnoticed accumulation of dust from processes.
AirSafe can be used as early detection for dust which could endanger the workplace.

Function

AirSafe consists of a flow duct and an integral triboelectric dust sensor.
A current of air is drawn through the duct at approximately 100 m3/h.
Dust particles, carried in the air current, passes the sensor, this generates a charge transfer, which is used as the measurement signal.
This signal is converted to electrical process outputs which could be used for display or control.

System
The AirSafe flow duct is 500 mm long and 100 x 100 mm square.
The integral dust sensor has a relay output which energises when the set limit value is exceeded.
The unit is supplied pre-calibrated.
The alert point is set to approximately 25 mg/m³ of dust.
The user can set his own alarm threshold.
This may be set within a range of approximately 5 mg/m³ to 150 mg/m³.
The alert point can be changed in steps of 5 mg by simply pressing a button.
As well as a contact closure output, the sensor also has an RS 485 output which can be connected to a wall mount or DIN rail mount transmitter.
The output from the transmitter is a standard 4 . . . 20 mA process output.
The transmitter also has a ModBus RTU RS 485 output which can also be used for connection to a PC.
By using the visualisation software, up to 10 measuring points can be displayed and saved and can be interfaced to other computer programs, e. g. Excel.

Mounting and Installation

AirSafe can be installed anywhere in a room.
Except of high ambient temperatures, there is no need to maintain distances from units or walls.

AirSafe can be wall-mounted using brackets provided.

Technical Data

AirSafe duct detector Measured objects Solid particles in a gas stream
  Particle size 0,3 µm or larger
  Measurement range from 0,1 mg/m<sup>3</sup>
  Ambient temperature - 20 . . . + 60 °C
  Humidity 95 % RH (non-condensing)
  Measurement principle Triboelectric
  Damping time 1 s
  Output signals Relay output, either NC or NO
  Dimensions 500 x 100 x 240 (L x B x H)
  Housing material Aluminium
  Power supply 24 ± 10 % V DC
  Rating Max. 10 W
  Electrical connection Screw terminals
  Weight 5,5 kg
     
Transmitter (DIN rail) Power supply 24 ± 10 % V DC
  Power consumption 20 W / 24 VA
  Protection type IP 40 to EN 60529
  Ambient operating temperature -10 … +45 °C
  Dimensions 23 x 90 x 118 (B x H x T)
  Weight Ca. 172 g
  Connection terminals cable cross-section 0,2 - 2,5 mm<sup>2</sup> [AWG 24-14]
  Current output 4 … 20 mA (0 … 20 mA), load < 500 Ω
  Switch output measurement alarm Relay with switchover contact, optional NC (opener) or NO (closer) - max. 250 V AC, 1 A
  Interface ModBus (RS 485)
  Data backup Flash-memory
     

Application Example

Click on a desired application example to navigate to a detailed description.

Dust monitoring
at spray dryer

Emergency shutdown
with AirSafe

Plant protection,
dust monitoring
with AirSafe

 
 